Mechanical Requests Detail (public view)
Permit Number: M3176003
Address 9200 UNIVERSITY CITY BLVD CHARLOTTE
Live Remote Inspection
CHARLOTTE
TCO Reinspection
Confirmation # 3176003007
Received Date Jul 26, 2018
Charge Reinspection Fee
Requested Date Jul 27, 2018 TCO Reinspection Fee:
Requested Through WEB
Email/Text Msg Addr: Jerman.aguirre@charlottemechanical.com
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jul 27, 2018
Result Overall Failed
Inspector Rosmon, Jeff
Inspector Phone # (980) 722-3680
Requested Tasks RF
OTI Details
OTI Start Time: (None)
OTI Duration: hrs
OTI Extend Hrs: hr(s) OTI Extension Fee: $0.00
Accept OTI Extension Reject OTI Extension
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
POSSE system power user requested rough inspection of Level 1-2-3 FSD installation only in firewalls betweeen A4 and A1 section also betweeen A4 and A3 section-failed- as discussed previously, walked with Rafael of Charlotte Mech. need fire caulk removed from damper sleeves and required gap openings in walls, holes at walls larger than dampers and angles, need penetration openings corrected, damper angles secured to structure, damper angle retaining screws missing, mineral wool packing at pipes within damper assembly (need to see detail)-need damper installation instructions so that I can help Rafael meet requirements 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467477