Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Mechanical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
M3176003
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
Live Remote Inspection
CHARLOTTE
TCO Reinspection
Confirmation #
3176003007
Received Date
Jul 26, 2018
Charge Reinspection Fee
Requested Date
Jul 27, 2018
TCO Reinspection Fee:
Requested Through
WEB
Email/Text Msg Addr:
Jerman.aguirre@charlottemechanical.com
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Jul 27, 2018
Result Overall
Failed
Inspector
Rosmon, Jeff
Inspector Phone #
(980) 722-3680
Requested Tasks
RF
OTI Details
OTI Start Time:
(None)
OTI Duration:
hrs
OTI Extend Hrs:
hr(s)
OTI Extension Fee:
$0.00
Accept OTI Extension
Reject OTI Extension
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
POSSE system power user
requested rough inspection of Level 1-2-3 FSD installation only in firewalls betweeen A4 and A1 section also betweeen A4 and A3 section-failed- as discussed previously, walked with Rafael of Charlotte Mech. need fire caulk removed from damper sleeves and required gap openings in walls, holes at walls larger than dampers and angles, need penetration openings corrected, damper angles secured to structure, damper angle retaining screws missing, mineral wool packing at pipes within damper assembly (need to see detail)-need damper installation instructions so that I can help Rafael meet requirements
1
RTAP Level:
(None)
RTAP Comments:
Submit
Cancel
Screen ID: 467477