Mechanical Requests Detail (public view)
Permit Number: M3176003
Address 9200 UNIVERSITY CITY BLVD CHARLOTTE
Live Remote Inspection
CHARLOTTE
TCO Reinspection
Confirmation # 3176003006
Received Date Jul 24, 2018
Charge Reinspection Fee
Requested Date Jul 25, 2018 TCO Reinspection Fee:
Requested Through WEB
Email/Text Msg Addr: Jerman.aguirre@charlottemechanical.com
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jul 25, 2018
Result Overall Failed
Inspector Rosmon, Jeff
Inspector Phone # (980) 722-3680
Requested Tasks RF
OTI Details
OTI Start Time: (None)
OTI Duration: hrs
OTI Extend Hrs: hr(s) OTI Extension Fee: $0.00
Accept OTI Extension Reject OTI Extension
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
POSSE system power user A-4 Shell FSD installation on level 1 only in firewalls between A4 and A1 section and A4 and A3 section and pool equipment room-failed- on fire smoke dampers, need holes in walls at damper angles repaired, need to maintain proper protection and clearance to other trade penetrations, damper actuator shafts need clearance, damper angles need to be tight to structure, no fire caulk at damper sleeve, pool equipment room ok, will need to verify chemical exhaust to pool courtyard 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467477