Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E3177699
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3177699025
TCO Reinspection
Received Date
Jan 8, 2019
Charge Reinspection Fee
Requested Date
Jan 9, 2019
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Jan 9, 2019
Result Overall
Failed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
FI
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
FI - Final Inspection
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Booth, Russell
Advantage Looked at C3 Shell Electrical FI 1) Previous defects not corrected 2) EMT not supported in storage room 3) Bonding wire not supported in storage room 4) Bonding wire to Telecom racks not supported *Notes C1 4th floor Electrical room: Telecom conduits in front of meter centers need to be removed