Electrical Requests Detail (public view)
Permit Number: E3177699
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3177699020 TCO Reinspection
Received Date Oct 30, 2018 Charge Reinspection Fee
Requested Date Oct 31, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 31, 2018
Result Overall Passed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 01 - Passed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Advantage Looked at C3 Shell IDF/MDF electrical for TC C3 IDF 1) 4th floor * LVC needs to bond the rack to the IS ground bar * EC Ok for TC 2) 3rd floor * IS bond to 4th floor under wrong lug size, * LVC needs to bond rack to IS ground bar 3) 2nd floor * no IDF equipment just FA * Support EMT * support # 250 CGE conductor 4) 1st floor 5) Breezeway IDF * DKing equipment needs bushings for KO?s * LVC needs to clean up LV cables around room wall 6) Generator room * EC ...OK for TC 7) Main IDF Rm * Need IS Bond ground bar * insulation under lug at CGE lug bar * FA labels on Ok 8) Main Elec Room * RP-4 and MC3 Main OCP needs AIC and seal conduits 9) C3 Stairwell #5 *1st - 5th levels Ok * 6th level no light diffuser 10) C3 is Ok for TC 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323