Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E3175970
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3175970031
TCO Reinspection
Received Date
Oct 30, 2018
Charge Reinspection Fee
Requested Date
Oct 31, 2018
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Oct 31, 2018
Result Overall
Passed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
01 - Passed
0
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Booth, Russell
Advantage Looked at A1 Shell IDF, MDF, Electrical rooms, Common areas electrical RF towards FI 1) 4th floor *IDF strap Ground Conductor *LVC needs to bond rack to IS ground bar *FA Panel needs circuit and panel labels 3rd floor * LVC needs to bond to IS ground bar 2nd floor *IDF closet LVC needs to bond the rack to the Inter-system ground bar 3) A1 Shell Ok for TC, including trash room, Fire pump room, domestic water and trash compactor room
0
RTAP Level:
(None)
RTAP Comments:
Submit
Cancel
Screen ID: 467323