RF - Rough Inspection 01 - Passed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Advantage Looked at A1 Shell IDF, MDF, Electrical rooms, Common areas electrical RF towards FI 1) 4th floor *IDF strap Ground Conductor *LVC needs to bond rack to IS ground bar *FA Panel needs circuit and panel labels 3rd floor * LVC needs to bond to IS ground bar 2nd floor *IDF closet LVC needs to bond the rack to the Inter-system ground bar 3) A1 Shell Ok for TC, including trash room, Fire pump room, domestic water and trash compactor room 0