Electrical Requests Detail (public view)
Permit Number: E3177694
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3177694019 TCO Reinspection
Received Date Oct 25, 2018 Charge Reinspection Fee
Requested Date Oct 26, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 26, 2018
Result Overall Passed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 01 - Passed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Advantage Looked at C2 Shell electrical RF towards TC 1) LP4 480/277v 100a MCB #1, #6G 2) Defects needed for Final * Label Panel and junction box * Permanent Panel schedule * need to identify the Neutral w/grey colored tape * Group the Neutral with the Phase conductor circuit * Identity Romex 480v colors in junction box * Conduit fitting missing a set screw * Ground Bar Terminations are not tight 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323