Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E3177694
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3177694019
TCO Reinspection
Received Date
Oct 25, 2018
Charge Reinspection Fee
Requested Date
Oct 26, 2018
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Oct 26, 2018
Result Overall
Passed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
01 - Passed
0
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Booth, Russell
Advantage Looked at C2 Shell electrical RF towards TC 1) LP4 480/277v 100a MCB #1, #6G 2) Defects needed for Final * Label Panel and junction box * Permanent Panel schedule * need to identify the Neutral w/grey colored tape * Group the Neutral with the Phase conductor circuit * Identity Romex 480v colors in junction box * Conduit fitting missing a set screw * Ground Bar Terminations are not tight