Electrical Requests Detail (public view)
Permit Number: E3199366
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3199366004 TCO Reinspection
Received Date Oct 18, 2018 Charge Reinspection Fee
Requested Date Oct 19, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 19, 2018
Result Overall Failed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Advantage Looked at Clubhouse electrical RF towards TC 1) Hard ceiling lights, receptacles at video wall & foyer column....Ok 2) Needed for TC * Receptacles need power in offices, kitchenette, entrance...recheck all * MC cabling needs to be supported above ceiling * Water cooler needs a GFI receptacle * Light fixtures need to see third party labeling on pendant and chandeliers * Recessed fixtures in lay-in ceiling need to be supported to structure * Front desk MC cabling needs to be installed in the furniture or safe-off until it arrives * Oil Minder box in wall no access hatch / is this a rated wall? 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323