Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E3199359
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3199359003
TCO Reinspection
Received Date
Oct 18, 2018
Charge Reinspection Fee
Requested Date
Oct 19, 2018
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Oct 19, 2018
Result Overall
Failed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Booth, Russell
Advantage Looked at the Fitness Center for electrical RF towards TC 1) receptacles, lights, GFI in bathroom...Ok 2) Needed for TC: * FA panels in IDF closet need to have the circuit and panel labels * The Panels and MSB need to have the labels and panel blanks installed * Light Fixture in Yoga room not installed * HVAC units in closets not marked (DBO) * Flexible conduit not correctly strapped above and below panels * Cracked cover plate * KO seal in junction box above doorway no correctly installed * Panel schedules/directories not installed
1
RTAP Level:
(None)
RTAP Comments:
Submit
Cancel
Screen ID: 467323