Electrical Requests Detail (public view)
Permit Number: E3199359
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3199359003 TCO Reinspection
Received Date Oct 18, 2018 Charge Reinspection Fee
Requested Date Oct 19, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 19, 2018
Result Overall Failed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Advantage Looked at the Fitness Center for electrical RF towards TC 1) receptacles, lights, GFI in bathroom...Ok 2) Needed for TC: * FA panels in IDF closet need to have the circuit and panel labels * The Panels and MSB need to have the labels and panel blanks installed * Light Fixture in Yoga room not installed * HVAC units in closets not marked (DBO) * Flexible conduit not correctly strapped above and below panels * Cracked cover plate * KO seal in junction box above doorway no correctly installed * Panel schedules/directories not installed 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323