Electrical Requests Detail (public view)
Permit Number: E3175970
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3175970027 TCO Reinspection
Received Date Sep 19, 2018 Charge Reinspection Fee
Requested Date Sep 20, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Sep 20, 2018
Result Overall Failed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 02 - Failed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
POSSE system power user Advantage Looked at A1 Shell 1st through 4th floor corridors electrical RF towards TC 1) 1st floor corridor Sconce Lts, EM Lts, Exit Lts, Receptacles...electrically Ok 2) 2nd floor corridor Sconce Lts, EM Lts, Exit Lts, Receptacles...electrically Ok 3) 3rd floor corridor Sconce Lts, EM Lts, Exit Lts, Receptacles...electrically Ok 4) 4th floor corridor Sconce Lts, EM Lts, Exit Lts, Receptacles ...electrically Ok 5) Common areas not included Defects to be corrected 1) 1st floor opening in ceiling exposed romex cabling and junction boxes (DBO) 2) 2nd floor opening in ceiling exposed MC Feeders (DBO) 3) 3rd floor near 3067 lighting outlet needs conductors identified as 277v and light installed 4) All levels re-purposed trash chute room needs sheetrock (DBO) 5) All levels various receptacles need arc shields in corridors 6) All levels the Unit Feeder Junction boxes in the ceiling need access covers & some boxes need to be re-labeled 7) All levels recheck Exit Lights some hanging due to damage by others, but operational 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323