Electrical Requests Detail (public view)
Permit Number: E3177694
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3177694014 TCO Reinspection
Received Date Sep 10, 2018 Charge Reinspection Fee
Requested Date Sep 11, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Sep 11, 2018
Result Overall Passed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 01 - Passed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Advantage Looked at Panel RP4 to energize lighting and receptacle circuits in C2/C3 corridors 1) RP4 fed from RDP in A2 2) 120/208v 250a OCP # 250Kcmil #3/0G Cu, spliced in OS Box to 500Kcmil 1/0G AL 3) Lighting circuits: 21, 23, 25, 27 4) Receptacle circuits: 1, 2, 3, 4, 5, 6, 7, 8 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323