Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E3175970
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3175970023
TCO Reinspection
Received Date
Sep 4, 2018
Charge Reinspection Fee
Requested Date
Sep 5, 2018
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Sep 5, 2018
Result Overall
Failed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
POSSE system power user
Advantage Looked at A1 Shell Jockey pump and Domestic Water pump electrical RF 1) Jockey pump controller needs to be labeled, seal-tight fittings are not secure, Ground strands not under lug in controller 2) Domestic Water disconnect not labeled, phase conductors improperly wired and marked (Grey and Blue), white conductor can not be re identified as a phase conducto, EGC only one per lug 3) Panel RP2 blanks missing, Labeling needed for circuits and panel