Electrical Requests Detail (public view)
Permit Number: E3176002
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3176002009 TCO Reinspection
Received Date Aug 29, 2018 Charge Reinspection Fee
Requested Date Aug 30, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Aug 30, 2018
Result Overall Failed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 02 - Failed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
POSSE system power user Advantage Looked at RDP 800a OCP feeding RP2 1) RP2 Section 600a MOCP (2) sets of #350 4/0G 2) Main Lug tap to RP2 Section 2 3) Ok to energize A1 and A4 120v lighting and receptacles *Receptacles circuits: 1, 2, 8, 9 *Lighting circuits: 65, 67, 69, 71 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323