Aug 29, 2018
Result Overall
Failed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
02 - Failed
0
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
POSSE system power user
Advantage Looked at C2/C3 Service Switch 1) 1600a MOCP, (5) sets of 600Kcmil from utility transformer 2) MBJ factory installed, 3/0GEC Ufer to ground bar, Common GEC 3) TU Application for TP completed...Ok to energize when defects by GC are corrected 4) GC has not sheet rocked the ceilings and walls where MC feeders are exposed The connect code cannot be sent for this Meter Center until all areas where MC Feeder cables are exposed is protected.