Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E3177694
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3177694011
TCO Reinspection
Received Date
Aug 21, 2018
Charge Reinspection Fee
Requested Date
Aug 22, 2018
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Aug 22, 2018
Result Overall
Passed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
01 - Passed
0
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Booth, Russell
Advantage Looked at C2/C3 Service Switch 1) 1600a MOCP, (5) sets of 600Kcmil from utility transformer 2) MBJ factory installed, 3/0GEC Ufer to ground bar, Common GEC 3) Complete the TU Application for TP