Electrical Requests Detail (public view)
Permit Number: E3177694
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3177694011 TCO Reinspection
Received Date Aug 21, 2018 Charge Reinspection Fee
Requested Date Aug 22, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Aug 22, 2018
Result Overall Passed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 01 - Passed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Advantage Looked at C2/C3 Service Switch 1) 1600a MOCP, (5) sets of 600Kcmil from utility transformer 2) MBJ factory installed, 3/0GEC Ufer to ground bar, Common GEC 3) Complete the TU Application for TP 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323