Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E3175986
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3175986016
TCO Reinspection
Received Date
Aug 17, 2018
Charge Reinspection Fee
Requested Date
Aug 18, 2018
TCO Reinspection Fee:
$0.00
Requested Through
Mecklenburg Staff
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Aug 20, 2018
Result Overall
Partial Approval
Inspector
Booth, Christopher
Inspector Phone #
(980) 722-3832
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
05 - Partial Approval
0
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Booth, Christopher
Saturday 8/18/18 A2 level 2 *** every unit needed breaker lock 2032 2034 2059 open neutral in receptacle CDI 2036 2061 2038 2063 2040 2065 2042 2067 1067 general receptacle spacing in bedroom. Needs to be checked 1042 1065 1040 1063 1038 1061 panel blank needed 1036 panel blanks needed 1059 1034 1032 panel blanks needed BldgA1 townhomes 1043: WH not wired and kitchen small appliance ckts feeding hallways on every floor 1-3? Smoke on level 3 too close to air vent, check all rooms and landing 1045: Same defects for kitchen ckt and smokes needed boxes under sink(Cdi) light in hallway not switched (cdi) Bedroom 3 missing outlet gen receptacle spacing. 2nd floor room on right and smoke locations. 1047- not ready, same as first two. Nothing further for townhomes today Saturday re inspection of A1 bldg. defects: 1030 fix gfci ok BUT STILL REQUIRE PANEL BLANKS 1028 microwave defect ok 1024 defects ok
0
RTAP Level:
(None)
RTAP Comments:
Submit
Cancel
Screen ID: 467323