Electrical Requests Detail (public view)
Permit Number: E3175986
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3175986016 TCO Reinspection
Received Date Aug 17, 2018 Charge Reinspection Fee
Requested Date Aug 18, 2018 TCO Reinspection Fee: $0.00
Requested Through Mecklenburg Staff
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Aug 20, 2018
Result Overall Partial Approval
Inspector Booth, Christopher
Inspector Phone # (980) 722-3832
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 05 - Partial Approval 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Christopher Saturday 8/18/18 A2 level 2 *** every unit needed breaker lock 2032 2034 2059 open neutral in receptacle CDI 2036 2061 2038 2063 2040 2065 2042 2067 1067 general receptacle spacing in bedroom. Needs to be checked 1042 1065 1040 1063 1038 1061 panel blank needed 1036 panel blanks needed 1059 1034 1032 panel blanks needed BldgA1 townhomes 1043: WH not wired and kitchen small appliance ckts feeding hallways on every floor 1-3? Smoke on level 3 too close to air vent, check all rooms and landing 1045: Same defects for kitchen ckt and smokes needed boxes under sink(Cdi) light in hallway not switched (cdi) Bedroom 3 missing outlet gen receptacle spacing. 2nd floor room on right and smoke locations. 1047- not ready, same as first two. Nothing further for townhomes today Saturday re inspection of A1 bldg. defects: 1030 fix gfci ok BUT STILL REQUIRE PANEL BLANKS 1028 microwave defect ok 1024 defects ok 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323