Electrical Requests Detail (public view)
Permit Number: E3175970
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3175970019 TCO Reinspection
Received Date Aug 7, 2018 Charge Reinspection Fee
Requested Date Aug 9, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Aug 9, 2018
Result Overall Passed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 01 - Passed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Arturo asked to move inspection to 8-9-18 before the Auto Notification was sent Advantage Looked at A1 Shell Fire Pump RF towards TP 1) 350Kcmil AL from Utility XFMR to meter, #4 bare CU GEC, (2) GE Rods 2) 250Kcmil CU 3/0 CU EGC from meter to FP controller OCP 225a 4) 2/0 Z cable 105* per table 360.60(C)(77) is 235a for the 50hp 208v 3ph motor, water is on the pipe 5) Ufer Ground, Common GEC, EGC terminated at ground bar in FP room 6) Need to bond the sprinkler pipe and TU application for TP 0