Permit Number:
E3175970
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3175970019
TCO Reinspection
Received Date
Aug 7, 2018
Charge Reinspection Fee
Requested Date
Aug 9, 2018
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Aug 9, 2018
Result Overall
Passed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
01 - Passed
0
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Booth, Russell
Arturo asked to move inspection to 8-9-18 before the Auto Notification was sent Advantage Looked at A1 Shell Fire Pump RF towards TP 1) 350Kcmil AL from Utility XFMR to meter, #4 bare CU GEC, (2) GE Rods 2) 250Kcmil CU 3/0 CU EGC from meter to FP controller OCP 225a 4) 2/0 Z cable 105* per table 360.60(C)(77) is 235a for the 50hp 208v 3ph motor, water is on the pipe 5) Ufer Ground, Common GEC, EGC terminated at ground bar in FP room 6) Need to bond the sprinkler pipe and TU application for TP