Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E3175970
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3175970018
TCO Reinspection
Received Date
Jul 31, 2018
Charge Reinspection Fee
Requested Date
Jul 31, 2018
TCO Reinspection Fee:
$0.00
Requested Through
Mecklenburg Staff
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Jul 31, 2018
Result Overall
Failed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
POSSE system power user
Review previous Fire Pump inspection notes The installation is not per the approved design drawings, an RTAP informal review is needed
1
RTAP Level:
Need Documentation Only
RTAP Comments:
The approved set of drawings shows a 480v FP, Controller etc. However, the EC installed a 208v 50hp FP and Controller/ATS
Engineer needs to provide the redesigned drawings in the field