Electrical Requests Detail (public view)
Permit Number: E3175970
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3175970018 TCO Reinspection
Received Date Jul 31, 2018 Charge Reinspection Fee
Requested Date Jul 31, 2018 TCO Reinspection Fee: $0.00
Requested Through Mecklenburg Staff
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jul 31, 2018
Result Overall Failed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
POSSE system power user Review previous Fire Pump inspection notes The installation is not per the approved design drawings, an RTAP informal review is needed 1
RTAP Level: Need Documentation Only
RTAP Comments: The approved set of drawings shows a 480v FP, Controller etc. However, the EC installed a 208v 50hp FP and Controller/ATS
Engineer needs to provide the redesigned drawings in the field
Screen ID: 467323