Permit Number:
E3175970
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3175970016
TCO Reinspection
Received Date
Jul 23, 2018
Charge Reinspection Fee
Requested Date
Jul 25, 2018
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Jul 25, 2018
Result Overall
Failed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
POSSE system power user
Looked at A1 Shell Fire Pump electrical RF Advantage 1) Per Arturo, the Fire Pump was designed to be a 480v but a they field installed a 208v 50hp with a 208v controller and transfer switch. Per 695.3(A) the FP will be energized by an individual source. No generator back-up power will be included 2) The EC needs to have engineered drawings and an RTAP for the above mentioned change showing the meter, OCP, feeder conductors, equipment grounding detail (etc.) 3) There is an Ufer ground and Common grounding conductor present but no ground bar for common grounding location, No EGC in the conduit to accommodate the change adding a meter, grounding terminations are incomplete 4) The 350kcmil AL conductors are not able to terminate in the OCPD in the controller 5) The Fire Pump is not ready for inspection