Electrical Requests Detail (public view)
Permit Number: E3175986
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3175986012 TCO Reinspection
Received Date Jul 20, 2018 Charge Reinspection Fee
Requested Date Jul 19, 2018 TCO Reinspection Fee: $0.00
Requested Through Mecklenburg Staff
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jul 20, 2018
Result Overall Passed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 01 - Passed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Correct Building A4 to A2 for RTU inspection 7-19-18 Looked at 120/208v MD gear on 1st floor and Meter Center on 2nd & 4th floors RF towards TP Advantage 1) 2000a MD on 1st floor from Utility (7) sets of 600kcmil AL 350kcmil AL Ground 2) 2000a OCP from MD feeds 2000a tap box for Meter Center on 2nd floor with 44 meters L / 28 meters R: 72 meters with 175a OCP for unit panels 3) 1600a MD on 1st floor Utility (6) sets of 750kcmil AL 350kcmil AL Ground 4) 1600a OCP from MD feeds 1600a tap box for Meter Center on 4th floor with 30 meters L / 28 meters R: 68 meters with 175a OCP for unit panels 5) 2nd and 4th floor electrical rooms have additional work space to allow for 1 personnel door, Warning labels installed. 6) Need locks and panic hardware installed on electrical room doors before TP 7) Meter Centers are phased, EC reconfigured the MC layouts, need Engineer to recalculate and approve before TP 8) Need to seal conduits entering from outside utility in MD's for TP 9) Need to see Common Grounding Electrode bonding for TP 10) Need to see Junction Box grounding for unit feeders for TP 11) 480v MDP 500kva XFMR, House Panels and Elevators are not included with this inspection 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323