Permit Number:
E3175986
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3175986011
TCO Reinspection
Received Date
Jul 17, 2018
Charge Reinspection Fee
Requested Date
Jul 19, 2018
TCO Reinspection Fee:
$0.00
Requested Through
Mecklenburg Staff
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Jul 19, 2018
Result Overall
Not Completed
Inspector
Booth, Russell
Inspector Phone #
(704) 574-8549
Requested Tasks
RF
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
RF - Rough Inspection
Not Done
0
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Lewis, Shiree
Looked at A4 Upfits RTU's and Meter Centers RF towards TC Advantage 1) Units * 1032-4032: MOCP 20a...NA * 1034-4034: MOCP 20a...NA * 1036-4036: MOCP 20a...NA * 1038-4038: MOCP 20a...NA * 1040-4040: MOCP 20a...NA * 1042-4042: MOCP 20a...NA * 1059-4059: Max OCP 30, Min OCP 25...Ok * 1061-4061: MOCP 20a...NA * 1063-4063: MOCP 20a...NA * 1065-4065: Max OCP 30, Min OCP 25...Ok * 1067-4067: Max OCP 30, Min OCP 25...Ok 2) Roof top safety switches, LFNC to condensers, labeling 3) EC needs to have permanent labels on units and disconnects, change the breakers in the units from 25a to 20a per MOCP on RTU nameplates 4) Meter Centers: Ran out of time doing RTU's for A2 need to schedule for inspection
0
RTAP Level:
(None)
RTAP Comments:
Submit
Cancel