Electrical Requests Detail (public view)
Permit Number: E3175986
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3175986011 TCO Reinspection
Received Date Jul 17, 2018 Charge Reinspection Fee
Requested Date Jul 19, 2018 TCO Reinspection Fee: $0.00
Requested Through Mecklenburg Staff
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jul 19, 2018
Result Overall Not Completed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection Not Done 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Lewis, Shiree Looked at A4 Upfits RTU's and Meter Centers RF towards TC Advantage 1) Units * 1032-4032: MOCP 20a...NA * 1034-4034: MOCP 20a...NA * 1036-4036: MOCP 20a...NA * 1038-4038: MOCP 20a...NA * 1040-4040: MOCP 20a...NA * 1042-4042: MOCP 20a...NA * 1059-4059: Max OCP 30, Min OCP 25...Ok * 1061-4061: MOCP 20a...NA * 1063-4063: MOCP 20a...NA * 1065-4065: Max OCP 30, Min OCP 25...Ok * 1067-4067: Max OCP 30, Min OCP 25...Ok 2) Roof top safety switches, LFNC to condensers, labeling 3) EC needs to have permanent labels on units and disconnects, change the breakers in the units from 25a to 20a per MOCP on RTU nameplates 4) Meter Centers: Ran out of time doing RTU's for A2 need to schedule for inspection 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323