Electrical Requests Detail (public view)
Permit Number: E3176002
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3176002007 TCO Reinspection
Received Date Jun 28, 2018 Charge Reinspection Fee
Requested Date Jun 29, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jun 29, 2018
Result Overall Partial Approval
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks AC
Results
Task Performed Result Billable to GC Affects HFR
Go
AC - Above Ceiling 05 - Partial Approval 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Booth, Russell Looked at A4 1st and 2nd floor corridors electrical AC Advantage 1) 1st floor corridors....Ok 2) 2nd floor Partial Approval * Corridor starting at Unit 2017 ending at Unit 2025, to B1 and B2 fire walls * MC Feeders not supported from Unit 2017 to A3 fire wall, need to see when finished * MC Feeders not supported from Unit 2025 to A1 fire wall, need to see when finished * MC Feeders not supported 15' back from B2 fire wall into A4 corridor, need to see when finished * MC Feeders at A4 / B1 fire wall ...Ok 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323