Electrical Requests Detail (public view)
Permit Number: E3176002
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3176002006 TCO Reinspection
Received Date Jun 20, 2018 Charge Reinspection Fee
Requested Date Jun 20, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr: Coronadoelect@gmail.com
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jun 20, 2018
Result Overall Failed
Inspector Booth, Russell
Inspector Phone # (704) 574-8549
Requested Tasks RF
Results
Task Performed Result Billable to GC Affects HFR
Go
RF - Rough Inspection 02 - Failed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
POSSE system power user Looked at A4 Shell 3rd & 4th floor corridors electrical RF Advantage 1) MC feeders, J-boxes and supports 2) GC needs to frame out access for feeder J-boxes...not approved 3) Missing framing members at corridor connections and with A1, A3 and B1....not approved 4) Ground screw in J-boxes needs to be replaced with a machine thread screw 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323