Electrical Requests Detail (public view)
Permit Number: E3205046
Address
6101 GLENRIDGE RD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3205046004 TCO Reinspection
Received Date Feb 21, 2018 Charge Reinspection Fee
Requested Date Feb 21, 2018 TCO Reinspection Fee: $100.00
Requested Through WEB
Email/Text Msg Addr: jputnam19@wmconnect.com
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Feb 26, 2018
Result Overall Failed
Inspector Williams, Joe
Inspector Phone # (980) 521-6623
Requested Tasks TP
Results
Task Performed Result Billable to GC Affects HFR
Go
TP - Temporary Power 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
POSSE system power user Install grounding electrode conductor to metal cold water pipe, main breaker too high/riser too low?, need access to main breaker, terminate all grounds and neutrals in sub-panel, install all sub-panel cover screws, sub-panel neutral bonded?, install breaker tie handle, protect cables as needed, terminate grounds correctly A/C disconnect, identify white wire A/C disconnect, install correct type wire to A/C unit from disconnect, need electrical contractor on site for information, job not ready, inspection incomplete. 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323