Building Requests Detail (public view)
Permit Number: B3177681
Address 9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation # 3177681036 TCO Reinspection
Received Date Oct 25, 2018 Charge Reinspection Fee
Requested Date Oct 26, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr: Lonny@spireusa.net
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 26, 2018
Result Overall Partial Approval
Inspector Koprivica, Milan
Inspector Phone # (704) 582-9481
Requested Tasks FR, RT
mecksectionheading
OTI Start Time: (None)
OTI Duration:
hrs
OTI Extend Hrs: hr(s) OTI Extension Fee: $0.00
Accept OTI Extension Reject OTI Extension
Results
Task Performed Result Partial Approval Note Billable to GC Affects HFR
Go
FR - Framing 05 - Partial Approval Scope of task is not complete. 0
Go
RT - Routine 05 - Partial Approval Scope of task is not complete. 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Koprivica, Milan installed shaft liner lid for inspect #3. Also talked to Lonny concerning doors at A3 - 45 minute fire door with glazing pending testing submittal per NFPA 80 of both glazing and door. And doors at 3 hour fire wall A3 - 03 series, 46 series, and ST1 series require 180 minute ratings for a 3 hour firewall, not 90 minute and labelled or on plans. And relocation of signage at interior stairs indicating floor level, roof access, level to exit discharge - acceptable locations interior stair for building/fire department. Also location of roof hatch access and rail requirements openings within 10'. 0
Koprivica, Milan installed shaft liner lid for inspect #3. Also talked to Lonny concerning doors at A3 - 45 minute fire door with glazing pending testing submittal per NFPA 80 of both glazing and door. And doors at 3 hour fire wall A3 - 03 series, 46 series, and ST1 series require 180 minute ratings for a 3 hour firewall, not 90 minute and labelled or on plans. And relocation of signage at interior stairs indicating floor level, roof access, level to exit discharge - acceptable locations interior stair for building/fire department. Also location of roof hatch access and rail requirements openings within 10'. 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467462