Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Building Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
B3175123
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3175123062
TCO Reinspection
Received Date
Oct 10, 2018
Charge Reinspection Fee
Requested Date
Oct 11, 2018
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Lonny@spireusa.net
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Oct 12, 2018
Result Overall
Failed
Inspector
Koprivica, Milan
Inspector Phone #
(704) 582-9481
Requested Tasks
FR
mecksectionheading
OTI Start Time:
(None)
OTI Duration:
hrs
OTI Extend Hrs:
hr(s)
OTI Extension Fee:
$0.00
Accept OTI Extension
Reject OTI Extension
Results
Task Performed
Result
Partial Approval Note
Billable to GC
Affects HFR
Go
FR - Framing
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Koprivica, Milan
A1/A2 shell corridors Ongoing construction not ready for prewalk to TCO Trash room not completed RTAP not completed, doors not closing RTAP storage rooms. Exit discharges and horizontal exit to A3 not completed Stairs not cleared of construction debris materials, fire doors not installed operational, hole in ceiling Typical Elevators not operating or completed 2 way not completed Fire exit hardware missing Door closer all mdf room Electrical rooms all not firestopped and Door closers not operating Exit signs missing above stair exit doors A1/A2 Bottom floor discharges not completed Ground level corridor not completed A2 Exit door needs separate release from mag lock, door needs to be completed Emergency generator not operational Elevators not operational typical Mags locks on exit doors need free release. Separate release Pics available This list is not comprehensive as inspection cannot be complete due to incomplete construction
1
RTAP Level:
(None)
RTAP Comments:
Submit
Cancel
Screen ID: 467462