Building Requests Detail (public view)
Permit Number: B3177681
Address 9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation # 3177681032 TCO Reinspection
Received Date Oct 3, 2018 Charge Reinspection Fee
Requested Date Oct 4, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr: Lonny@spireusa.net
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 4, 2018
Result Overall Failed
Inspector Koprivica, Milan
Inspector Phone # (704) 582-9481
Requested Tasks FR
mecksectionheading
OTI Start Time: (None)
OTI Duration:
hrs
OTI Extend Hrs: hr(s) OTI Extension Fee: $0.00
Accept OTI Extension Reject OTI Extension
Results
Task Performed Result Partial Approval Note Billable to GC Affects HFR
Go
FR - Framing 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Koprivica, Milan Exit passageway drop ceiling No communicating equipment can be located in exit passageway, electrical junction boxes per 1027 NCBC. Ductwork not completed from corridor to passageway and not allowed to communicate in exit passageway. HVAC must be independent serving only passageway Need to relocate /address with designers 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467462