POSSE system power user |
C1 levels 1 & 2 pre walk - units not completed.
1115-1118,1201-,2115-2118,2201,
Fire caulk needed at bathroom pipes corridor walls B corner units
1118 is fit out as Type A unit with unfinished grab bars, but kitchen sink not 34? max, bathroom sink not 34?, need pipe protection, sinks not removable Type A or B?
Reassess number of type a units for structure, missing thresholds.
No 30? clear floor space at alcove sink, need pipe protection.
Transfer shower not 36? min wide for type A or B
1116
Missing thresholds, pipe fire caulk bathrooms
1115 missing thresholds, fire caulk pipes
1117 Type A with grab bars, need pipe protection, missing vertical grab bars
Kitchen sink more than 34?, window sill repair
Transfer shower not 36? wide for type A or B
Missing thresholds
1117 and 1118 fit out as type A with unfinished grab bars. Remove toilet grab bars. Need to see list of revised Type A locations.
2115, 2117 pipe FC
2116 door closer, pipe FC
2118 ok
|
|
0 |
|
|
|
|
|
|
|
|
|
|
|
|
|