Building Requests Detail (public view)
Permit Number: B3177681
Address 9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation # 3177681023 TCO Reinspection
Received Date Aug 16, 2018 Charge Reinspection Fee
Requested Date Aug 17, 2018 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr: Lonny@spireusa.net
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Aug 20, 2018
Result Overall Failed
Inspector Koprivica, Milan
Inspector Phone # (704) 582-9481
Requested Tasks FR
mecksectionheading
OTI Start Time: (None)
OTI Duration:
hrs
OTI Extend Hrs: hr(s) OTI Extension Fee: $0.00
Accept OTI Extension Reject OTI Extension
Results
Task Performed Result Partial Approval Note Billable to GC Affects HFR
Go
FR - Framing 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
POSSE system power user C3 exit passageway ceiling 1st layer and RC ok, except open hole at beam location and gap. And 2 hour fire barrier wall not installed/ not extending above ceiling at alcove area at unit 1201 and ceiling covers access, remove ceiling portion to build fire barrier to underside floor deck above. How is sheetrock joining beam with joint, firestopping? Will Need 90 minute door at unit Need draftstop mineral wool at cmu walls before hanging, exposed stud and column dead space corner needs to be covered also with 2 hour fire barrier. SFRM patching must be done at beam and column Beam and sheetrock need to provide UL fire joint detail 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467462