Welcome
WebPermit 7.3
View Permits
|
Links
|
Sign In
Building Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
B3199262
Address
9200 UNIVERSITY CITY BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
3199262017
TCO Reinspection
Received Date
May 16, 2018
Charge Reinspection Fee
Requested Date
May 17, 2018
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
Lonny@spireusa.net
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
May 17, 2018
Result Overall
Failed
Inspector
Koprivica, Milan
Inspector Phone #
(704) 582-9481
Requested Tasks
FR
mecksectionheading
OTI Start Time:
(None)
OTI Duration:
hrs
OTI Extend Hrs:
hr(s)
OTI Extension Fee:
$0.00
Accept OTI Extension
Reject OTI Extension
Results
Task Performed
Result
Partial Approval Note
Billable to GC
Affects HFR
Go
FR - Framing
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
POSSE system power user
Unit 1201 Door opening J2 needs 2 jack studs 2 Windows J3E needs 3 jack studs H4 window header is H1 split window with J2 both sides and middle, RFI 102. Top plate at shear wall calls out 3 (2x6) and truss girder F77 over door header requires 3 full height studs Need to address w engineer Missing 2 anchor bolts Unit 2201 Need H4 header 3(2x12) Need engineer to address F77 truss girder over door header no full height 3 stud pack and 3(2x6) top plate missing at shear wall side Need 4 pack under truss girder F77 at cmu side wall. Required to address all fixes prior to insulation inspection.
1
RTAP Level:
(None)
RTAP Comments:
Submit
Cancel
Screen ID: 467462