Permit Number:
E4797932
Address
8800 E W T HARRIS BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
4797932013
TCO Reinspection
Received Date
Oct 21, 2025
Charge Reinspection Fee
Requested Date
Oct 22, 2025
TCO Reinspection Fee:
$0.00
Requested Through
IVR
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Oct 22, 2025
Result Overall
Failed
Inspector
McCall, Travis
Inspector Phone #
(980) 722-1421
Requested Tasks
FI
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
FI - Final Inspection
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
McCall, Travis
1) Still need GFCI protection per 210.8 on rotisserie fed from panel L1D4 section 1 circuits 13,15,17,19 2) Panels not labeled - name, volt, fed from, arc flash 3) Need panel name and circuit numbers on all disconnects/receptacles/equipment 4) Equipment grounds in Panel H1B must be isolated from the neutral bar and bonded to the can 5) Grounding electrode (steel) in trans to L1D4 must terminate to grounding terminal and a supply side bonding jumper ran from the terminal to XO per 450/250