Electrical Requests Detail (public view)
Permit Number: E4797932
Address
8800 E W T HARRIS BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 4797932013 TCO Reinspection
Received Date Oct 21, 2025 Charge Reinspection Fee
Requested Date Oct 22, 2025 TCO Reinspection Fee: $0.00
Requested Through IVR
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 22, 2025
Result Overall Failed
Inspector McCall, Travis
Inspector Phone # (980) 722-1421
Requested Tasks FI
Results
Task Performed Result Billable to GC Affects HFR
Go
FI - Final Inspection 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
McCall, Travis 1) Still need GFCI protection per 210.8 on rotisserie fed from panel L1D4 section 1 circuits 13,15,17,19 2) Panels not labeled - name, volt, fed from, arc flash 3) Need panel name and circuit numbers on all disconnects/receptacles/equipment 4) Equipment grounds in Panel H1B must be isolated from the neutral bar and bonded to the can 5) Grounding electrode (steel) in trans to L1D4 must terminate to grounding terminal and a supply side bonding jumper ran from the terminal to XO per 450/250 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323