Mechanical Requests Detail (public view)
Permit Number: M4828794
Address 8800 E W T HARRIS BLVD CHARLOTTE
Live Remote Inspection
CHARLOTTE
TCO Reinspection
Confirmation # 4828794001
Received Date Oct 21, 2025
Charge Reinspection Fee
Requested Date Oct 22, 2025 TCO Reinspection Fee:
Requested Through WEB
Email/Text Msg Addr: jason.hohenstein@psi.works
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 22, 2025
Result Overall Failed
Inspector Clark, Ryan
Inspector Phone # (704) 619-3744
Requested Tasks GT
OTI Details
OTI Start Time: (None)
OTI Duration: hrs
OTI Extend Hrs: hr(s) OTI Extension Fee: $0.00
Accept OTI Extension Reject OTI Extension
Results
Task Performed Result Billable to GC Affects HFR
Go
GT - Gas Test (Air Test On Gas Pipe) 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Clark, Ryan Testing through regulator not allowed, 2psi regulator has been installed on roof for new gas line to oven, building pressure is 5 psi, OPD is required. New tie ins have been installed on roof to new and existing RTUs, need whether proof vent caps on regulators, remove bushing fitting in test tees. Need additional supports and 5psi labels on on new gas piping Need to request a (PS) pipe service task with next gas test 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467477