Permit Number:
M4828794
Address
8800 E W T HARRIS BLVD CHARLOTTE
Live Remote Inspection
CHARLOTTE
TCO Reinspection
Confirmation #
4828794001
Received Date
Oct 21, 2025
Charge Reinspection Fee
Requested Date
Oct 22, 2025
TCO Reinspection Fee:
Requested Through
WEB
Email/Text Msg Addr:
jason.hohenstein@psi.works
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Oct 22, 2025
Result Overall
Failed
Inspector
Clark, Ryan
Inspector Phone #
(704) 619-3744
Requested Tasks
GT
OTI Details
OTI Start Time:
(None)
OTI Duration:
hrs
OTI Extend Hrs:
hr(s)
OTI Extension Fee:
$0.00
Accept OTI Extension
Reject OTI Extension
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
GT - Gas Test (Air Test On Gas Pipe)
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Clark, Ryan
Testing through regulator not allowed, 2psi regulator has been installed on roof for new gas line to oven, building pressure is 5 psi, OPD is required. New tie ins have been installed on roof to new and existing RTUs, need whether proof vent caps on regulators, remove bushing fitting in test tees. Need additional supports and 5psi labels on on new gas piping Need to request a (PS) pipe service task with next gas test