Permit Number: E4797932
Address
8800 E W T HARRIS BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 4797932012 TCO Reinspection
Received Date Oct 13, 2025 Charge Reinspection Fee
Requested Date Oct 14, 2025 TCO Reinspection Fee: $0.00
Requested Through IVR
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 15, 2025
Result Overall Failed
Inspector McCall, Travis
Inspector Phone # (980) 722-1421
Requested Tasks FI
Results
Task Performed Result Billable to GC Affects HFR
Go
FI - Final Inspection 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
McCall, Travis 1) No panel schedules - cannot verify any equipment 2) Panels not labeled - name, volt, fed from, arc flash 3) New 480 panel, trans and feed to 208 panels have not been inspected, this must all be shut off to be inspected, contractor must be on site 4) No gfci on 3 ph cord and plug ovens that I can find 5) Need panel name and circuit numbers on all disconnects/receptacles 6) Need to check em lights, and new roof equipment This is not a complete inspection - this area cannot be occupied until inspections have passed 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323