Welcome
WebPermit (A)
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E4797932
Address
8800 E W T HARRIS BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
4797932012
TCO Reinspection
Received Date
Oct 13, 2025
Charge Reinspection Fee
Requested Date
Oct 14, 2025
TCO Reinspection Fee:
$0.00
Requested Through
IVR
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Oct 15, 2025
Result Overall
Failed
Inspector
McCall, Travis
Inspector Phone #
(980) 722-1421
Requested Tasks
FI
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
FI - Final Inspection
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
McCall, Travis
1) No panel schedules - cannot verify any equipment 2) Panels not labeled - name, volt, fed from, arc flash 3) New 480 panel, trans and feed to 208 panels have not been inspected, this must all be shut off to be inspected, contractor must be on site 4) No gfci on 3 ph cord and plug ovens that I can find 5) Need panel name and circuit numbers on all disconnects/receptacles 6) Need to check em lights, and new roof equipment This is not a complete inspection - this area cannot be occupied until inspections have passed
1