Electrical Requests Detail (public view)
Permit Number: E4797932
Address
8800 E W T HARRIS BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 4797932009 TCO Reinspection
Received Date Oct 6, 2025 Charge Reinspection Fee
Requested Date Oct 7, 2025 TCO Reinspection Fee: $0.00
Requested Through IVR
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 7, 2025
Result Overall Failed
Inspector McCall, Travis
Inspector Phone # (980) 722-1421
Requested Tasks AC
Results
Task Performed Result Billable to GC Affects HFR
Go
AC - Above Ceiling 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
McCall, Travis Defects Not Corrected 1) Seal inside of raceways passing through cooler/freezer ceiling or walls - for temperature change to reduce/eliminate condensation inside conduit 2) Box(es) over filled on top of cooler, need extension rings 3) Boxes not grounded on top of coolers/freezer 4) MC cable still coiled and not terminated 5) MC cable cut off hanging out of wall above sink at BoH entrance 6) Remove abandoned temporary lights and wiring above ceiling 7) Junction box with wires and wire nuts hanging out of box to right of single cooler 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323