Welcome
WebPermit (A)
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E4797932
Address
8800 E W T HARRIS BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
4797932008
TCO Reinspection
Received Date
Oct 3, 2025
Charge Reinspection Fee
Requested Date
Oct 6, 2025
TCO Reinspection Fee:
$0.00
Requested Through
IVR
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Oct 6, 2025
Result Overall
Failed
Inspector
McCall, Travis
Inspector Phone #
(980) 722-1421
Requested Tasks
AC
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
AC - Above Ceiling
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
McCall, Travis
1) All 2 x 2 fixtures must be supported on 2 opposite corners and the tie wire must be secured at both ends ( several just hooked over bar joist 2) MC cable not terminated near door into BoH 3) Seal inside of all conduits penetrating all walk in coolers/freezer 4) Need strain reliefs on SO cords All LV (others) also needs to be completed AC and have inspections (several issues with LV) cooler/freezer controls, audio, data, etc.
1
RTAP Level:
(None)
RTAP Comments:
Submit
Cancel
Screen ID: 467323