Mechanical Requests Detail (public view)
Permit Number: M4688716
Address 14523 CAROWINDS BLVD CHARLOTTE
Live Remote Inspection
CHARLOTTE
TCO Reinspection
Confirmation # 4688716001
Received Date Oct 8, 2024
Charge Reinspection Fee
Requested Date Oct 9, 2024 TCO Reinspection Fee:
Requested Through WEB
Email/Text Msg Addr: Wpage@team-mech.com
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Oct 9, 2024
Result Overall Failed
Inspector Winslow, Mark
Inspector Phone # (980) 310-6054
Requested Tasks FI, GT
OTI Details
OTI Start Time: (None)
OTI Duration: hrs
OTI Extend Hrs: hr(s) OTI Extension Fee: $0.00
Accept OTI Extension Reject OTI Extension
Results
Task Performed Result Billable to GC Affects HFR
Go
FI - Final Inspection 02 - Failed 1
Go
GT - Gas Test (Air Test On Gas Pipe) 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Winslow, Mark Switching from propane to natural gas for gas pack. All new work must be painted Gas pipe needs to be clear of the ground by at least 4 inches. Cannot test through a regulator Weatherproof vent limiter Label gas pipe Flex connector should connect outside of the appliance Drip leg needs to be installed between shutoff and regulator 1
Winslow, Mark Switching from propane to natural gas for gas pack. All new work must be painted Gas pipe needs to be clear of the ground by at least 4 inches. Cannot test through a regulator Weatherproof vent limiter Label gas pipe Flex connector should connect outside of the appliance Drip leg needs to be installed between shutoff and regulator 1