Electrical Requests Detail (public view)
Permit Number: E4171766
Address
14523 CAROWINDS BLVD CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 4171766002 TCO Reinspection
Received Date Jun 1, 2022 Charge Reinspection Fee
Requested Date Jun 2, 2022 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr: tommy@wecosc.com
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jun 2, 2022
Result Overall Failed
Inspector Metcalf, Travis
Inspector Phone # (980) 721-4764
Requested Tasks FI
Results
Task Performed Result Billable to GC Affects HFR
Go
FI - Final Inspection 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Metcalf, Travis - Need either a low voltage permit or electrician needs to amend permit taking responsibility - Need ground rods for service on separate structure - Need panels labeled properly - Need showroom window receptacles on dedicated circuits - Need to verify no building steel and water bond - Need the exit lights on room lighting circuit Inspection stopped. Job not ready 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323