Welcome
WebPermit 7.4
View Permits
|
Links
|
Sign In
Electrical Requests Detail (public view)
Submit
Cancel
JavaScript and Session Cookies must be enabled for this Site.
Permit Number:
E4171766
Address
14523 CAROWINDS BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation #
4171766002
TCO Reinspection
Received Date
Jun 1, 2022
Charge Reinspection Fee
Requested Date
Jun 2, 2022
TCO Reinspection Fee:
$0.00
Requested Through
WEB
Email/Text Msg Addr:
tommy@wecosc.com
Homeowner Priority:
Homeowner Name:
Phone:
( ) -
Result Date
Jun 2, 2022
Result Overall
Failed
Inspector
Metcalf, Travis
Inspector Phone #
(980) 721-4764
Requested Tasks
FI
Results
Task Performed
Result
Billable to GC
Affects HFR
Go
FI - Final Inspection
02 - Failed
1
Inspector Comments
Last Update By
Inspectors Notes
Chargeable Failure
Affects HFR
Metcalf, Travis
- Need either a low voltage permit or electrician needs to amend permit taking responsibility - Need ground rods for service on separate structure - Need panels labeled properly - Need showroom window receptacles on dedicated circuits - Need to verify no building steel and water bond - Need the exit lights on room lighting circuit Inspection stopped. Job not ready
1
RTAP Level:
(None)
RTAP Comments:
Submit
Cancel
Screen ID: 467323