Electrical Requests Detail (public view)
Permit Number: E3900351
Address
4400 SHARON RD Unit: N14A CHARLOTTE
CHARLOTTE Live Remote Inspection
Confirmation # 3900351003 TCO Reinspection
Received Date May 13, 2021 Charge Reinspection Fee
Requested Date May 14, 2021 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date May 14, 2021
Result Overall Failed
Inspector Arambula, Jesse
Inspector Phone # (704) 634-8849
Requested Tasks AC
Results
Task Performed Result Billable to GC Affects HFR
Go
AC - Above Ceiling 02 - Failed 1
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Arambula, Jesse 1) Support conduits at LV lighting gutter 2) Support MC cable properly throughout 3) MC HCF cable will not meet requirements for isolated ground circuits 1
RTAP Level: (None)
RTAP Comments:
Screen ID: 467323