Mechanical Requests Detail (public view)
Permit Number: M3430584
Address 14523 CAROWINDS BLVD CHARLOTTE
Live Remote Inspection
CHARLOTTE
TCO Reinspection
Confirmation # 3430584008
Received Date Jul 25, 2019
Charge Reinspection Fee
Requested Date Jul 29, 2019 TCO Reinspection Fee:
Requested Through WEB
Email/Text Msg Addr: sherry@perrigoheating.com
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jul 29, 2019
Result Overall Passed
Inspector Hardin, Jimmy
Inspector Phone # (704) 634-1400
Requested Tasks FI, RH
OTI Details
OTI Start Time: (None)
OTI Duration: hrs
OTI Extend Hrs: hr(s) OTI Extension Fee: $0.00
Accept OTI Extension Reject OTI Extension
Results
Task Performed Result Billable to GC Affects HFR
Go
FI - Final Inspection 01 - Passed 0
Go
RH - Restaurant Hood Gas Test 01 - Passed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Hardin, Jimmy Job ready for final. Hood performance test. Design exhaust 6130 Actual exhaust 6201 Design supply 5520 Actual supply 5853 0
Hardin, Jimmy Job ready for final. Hood performance test. Design exhaust 6130 Actual exhaust 6201 Design supply 5520 Actual supply 5853 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467477