Building Requests Detail (public view)
Permit Number: B3402742
Address 14523 CAROWINDS BLVD CHARLOTTE
CHARLOTTE
Live Remote Inspection
Confirmation # 3402742059 TCO Reinspection
Received Date Jul 8, 2019 Charge Reinspection Fee
Requested Date Jul 9, 2019 TCO Reinspection Fee: $0.00
Requested Through WEB
Email/Text Msg Addr:
Homeowner Priority:
Homeowner Name: Phone: (   )    -    
Result Date Jul 9, 2019
Result Overall Failed
Inspector Tomasino, Nick
Inspector Phone # (704) 560-9589
Requested Tasks TC
mecksectionheading
OTI Start Time: (None)
OTI Duration:
hrs
OTI Extend Hrs: hr(s) OTI Extension Fee: $0.00
Accept OTI Extension Reject OTI Extension
Results
Task Performed Result Partial Approval Note Billable to GC Affects HFR
Go
TC - Temporary Occupancy 02 - Failed 0
Inspector Comments
Last Update By Inspectors Notes Chargeable Failure Affects HFR
Tomasino, Nick Dorm building only Items on last inspection has been corrected Revise egress light letter and fire sprinkler certification showing building address. Second floor men?s shower has curb in place Ada showers and ambulatory stalls missing vertical bars Egress stair side missing floor identification Third floor mechanical room has penitrations in floor and roof assembly. Must screw heads on third floor Sheetrock ceiling Third floor it room has spray foam in place for fire stopping Mechanical shafts areas trough floor. Floor flutes are not seal. Provide assembly to fire rate. Interior stair shaft bottom exit missing required exit sign. 0
RTAP Level: (None)
RTAP Comments:
Screen ID: 467462